Technical note · 4 Nov 2026 · 6 min read

Sizing VRF systems for Indian part-load conditions

Nameplate capacity tells you almost nothing about how a residential tower will run. Here are the diversity factors we use, and why.

NSName Surname
Senior HVAC Engineer, Indore

Refrigerant pipework and ductwork in a ceiling void

Most VRF systems in Indian residential towers are selected at design-day conditions with every apartment occupied, every window closed and every indoor unit calling for full cooling. That day never arrives. What arrives instead is a building running at 30 to 55 percent of installed capacity for most of the year, with outdoor units cycling, compressors short-running and efficiency well below catalogue.

Where the standard method goes wrong

The usual approach applies a single diversity factor, often 0.7 or 0.8, to the sum of indoor unit capacities. That factor is borrowed from commercial practice and it ignores three things that matter in Indian residential buildings: occupancy that peaks at night, orientation that moves the load around the floor plate through the day, and tenants who treat the system as on-off rather than as a thermostat.

Design for the evening the building will have, not the afternoon it never will.

The factors we use

We build an hourly load profile for each apartment type and orientation, then combine them to find the coincident peak for each outdoor unit. On a typical 30-storey tower this lands between 0.55 and 0.65 of connected capacity, depending on the mix of two- and three-bedroom units.

Diversity applied to outdoor units on a typical 30-storey tower
Outdoor unit servesConnected, kWCoincident peak, kWDiversity
2 BHK, east facing84490.58
2 BHK, west facing84540.64
3 BHK, east facing112630.56
3 BHK, west facing112720.64
Corner 3 BHK, two facades126820.65
Outdoor unit platform on a residential tower
Outdoor units grouped by orientation, so each system sees a similar load curve.

What changes on site

Smaller outdoor units that run nearer their best efficiency, fewer compressor starts and a lower electrical connected load. On the last three towers we measured, part-load efficiency improved by 12 to 18 percent against the original selection.